* УТОЧНЯЙТЕ ВОЗМОЖНОСТЬ, ЦЕНУ И СРОК ПОСТАВКИ, В СВЯЗИ С ОГРАНИЧЕНИЕМ ЭКСПОРТА ТОВАРОВ ИЗ СТРАН ЕС И ВЕЛИКОБРИТАНИИ
G9SA, Safety Relays, Expandable
The G9SA family offers a line-up of compact and expandable safety relay units. Modules with safe OFF-delay timing are available as well as a two hand controller. Simple multiplication of safety contacts is possible by using the connection on the front.
45mm wide housing, expansion units are 17.5mm wide
Both DIN mount and screw mount are possible
Safe OFF-delay timer model with 1-15s delay (in 1s steps)
Simple expansion connection
Certification up to category 4 according to EN954-1 depending on the application
Suitable for PNP OSSD outputs of safety sensors, F3SN, F3SH, F3S-B, F3S-TGR, F3SL
Standards
EN954-1, EN60204-1, EN574 (-TH301), UL508, CSA C22.2 No. 14
Approvals
UL, CSA
G9SA Compact Expandable Safety Relays.
•Compact.
•Four relay types of 45 mm widths available.
•3-pole, 5-pole, models with 3-poles and 2 OFF-delay poles plus 2-hand controller.
•Also available are the 17.5mm wide relay expansion units with 3-poles and 3 OFF-delay poles.
•Easy expansion connection.
•OFF-delay safety relay models have 15-step OFF-delay settings.
•Conforms to EN ISO 13849-1 (PLe/safety category 4)
•DIN rail mounting and Screw mounting.
•Used for most safety relay applications within the industrial automation industry.
G9SA Safety Relay Series Explained.
•G9SA -301 or G9SA-501 – Relay Emergency Stop Units.
•G9SA-321- T – Relay Emergency Stop OFF-delay units.
•G9SA-TH – Relay Two-hand Controller.
•G9SA-EX301 – Relay Expansion Units.
•G9Sa-EX031 – Relay Expansion Units with OFF-delay Outputs.
G9SA-501 AC100-240 Emergency Stop Safety Relay.
•Main contact 5PST-NO (normally open).
•Auxiliary contact SPST-NC (normally closed).
•1 Channel or 2 Channels possible.
•Rated voltage 100 to 240 V ac.
•Operating voltage range 85% to 110% of the rated power supply voltage.
•Power consumption 100 to 240 V ac, 11 VA max.
•When an expansion unit is connected the power consumption is increased by 2 VA/2 W max.
•Input current 60 mA max.
•Resistive load
•Rated load 250 V ac, 5 A. 30 V dc, 5 A.
•Rated carry current 5 A.
Features and Benefits.
•Contact resistance 100 mΩ
•Insulation resistance 100 MΩ mon (at 500 V dc)
•Vibration resistance 10 to 55 to 10 Hz, 0.275 mm single amplitude (0.75 mm double amplitude)
•Shock resistance destruction 300 m/s².
•Shock resistance malfunction 100 m/s²
•Failure rate (P Level) (reference value) 5 V dc, 1 mA
•Weight 270 g. (for 24 ac/dc)
•Weight 290 g. (for 100 to 240 V ac)
•Do Not remove the connector of this model unless an expansion unit is being connected.
•Always turn OFF the G9SA before connecting an expansion unit.
•If mounting multiple units next to each other the rated current will be 3 A. (do not apply any higher currents)
Standards
EN 954-1, EN 60204-1, UL 508, CSA C22.2 No 14, EN 55011 group 1 class A, EN 50082-2 group 1.
Техническая спецификацияMachine Guarding and Safety Range Overview
Omron Machine Safety
G9SA
G9SA Datasheet
Самовывоз со склада поставщика в Екатеринбурге | Забираете сами или вызываете курьера |
ТК Деловые Линии | от 500 руб |
Курьером EMS Почта России | от 500 руб |
Другой транспортной компанией | По согласованию |